کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
649391 | 1457214 | 2007 | 6 صفحه PDF | دانلود رایگان |

A critical cycle heat pump with HFC125 was studied experimentally. The experimental result indicates that the heat pump with HFC125 can use the general components of the conventional heat pump well. Hot water with wide-range temperature can be conveniently got by the critical heat pump system through water flow control. The COPh of the critical cycle drops a little when the temperature of outlet water rises from 60 °C to 75 °C. And adding heat recovering exchanger cannot improve the performance of the cycle, but can reduce the working pressure of the cycle. Comparing with the CO2 trans-critical heat pump, HFC125 critical heat pump has a better performance of refrigeration, lower working pressure, which is especially suitable for dual-function of supplying hot water and refrigeration in the civil and industrial buildings.
Journal: Applied Thermal Engineering - Volume 27, Issues 5–6, April 2007, Pages 988–993