کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
649437 | 1457213 | 2007 | 6 صفحه PDF | دانلود رایگان |

The temperature of the water returning from the network affects greatly the efficiency of a geothermal district-heating system (GDHS). The temperature of the returning water depends on whether there is a heat exchanger between network flow and indoor circulation. The return temperature also depends on outdoor temperature and logic of the indoor temperature control system. In this paper, four control logics are defined depending on whether indoor circulation is separated from network circulation or not. Return temperature and circulation rate of network flow are calculated for these control logics. The results show that the flow rate of the network flow and annual consumption of the geothermal fluid could be decreased about 10% or over by using optimum control logic in district heating systems.
Journal: Applied Thermal Engineering - Volume 27, Issues 8–9, June 2007, Pages 1495–1500