Analysis of fouling factor in district heating heat exchangers with parallel helical tube coils
چکیده انگلیسی

This paper presents the results of measurements of thermal performance of 8 heat exchangers with parallel helical coils. Measurements were conducted in substations in 2 district heating systems in Serbia: Belgrade and Sremska Mitrovica. The values of fouling resistances were found to be slightly lesser than usual values for typical shell-and-tube heat exchangers with straight tubes. Analysis of thermal performance of heat exchangers showed that the shell-side heat transfer coefficient can be calculated using the correlation based on hydraulic diameter.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Heat and Mass Transfer - Volume 57, Issue 1, 15 January 2013, Pages 9–15