کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
669193 1458809 2008 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Homogeneous versus separated two phase flow models: Adiabatic capillary tube flow in a transcritical CO2 heat pump
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Homogeneous versus separated two phase flow models: Adiabatic capillary tube flow in a transcritical CO2 heat pump
چکیده انگلیسی

A comparative study of flow characteristics of an adiabatic capillary tube in a transcritical CO2 heat pump system have been investigated employing separated and homogeneous two phase flow models. Separated flow model is employed considering the annular flow pattern. The models are based on fundamental equations of mass, momentum and energy which are solved simultaneously. Two friction factor empirical correlations (Churchill, Lin et al.) and McAdams viscosity model are used. Chisholm correlation is used to calculate slip ratio while void fraction is calculated based on Premoli correlation. Sub-critical and super-critical thermodynamic and transport properties of CO2 are calculated employing a precision in-house property code.The results indicate that both two phase flow models predict reasonably well. Discrepancy between the separated flow model and homogeneous flow model has a maximum about 8 to 11%. Void fraction is influenced by vapour quality and follows the same trend as vapour quality. Liquid velocity and vapour velocity difference is relatively lower compared to R22.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Thermal Sciences - Volume 47, Issue 11, November 2008, Pages 1555-1562