The experiment in terms of heat transfer performance of natural draft counter-flow wet cooling is done for cases with cross-wind conditions. The variation of circulating-water temperature difference (ΔT) and cooling coefficient of efficiency (η) with cross-wind velocity, circulating water inlet temperature and flow rate, are shown under cross-wind conditions, compared with cases without wind. According to experimental results, it is found that ΔT and η are influenced by the cross-wind, and ΔT and η can decrease mostly by 6% and 5%, respectively. When the critical Frl number is less than 0.174, ΔT and η decrease with increasing cross-wind velocity, however, when it is greater than 0.174, ΔT and η increase with increasing cross-wind velocity. In addition, based on the data regression analysis, the correlation between ΔT, η and parameters, such as circulating-water inlet temperature and flow rate, is derived for cases with windless conditions. Furthermore, its correspondence is given out for cases with cross-wind conditions.
Journal: International Journal of Thermal Sciences - Volume 47, Issue 7, July 2008, Pages 935-941