کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
7048756 | 1457135 | 2016 | 23 صفحه PDF | دانلود رایگان |
عنوان انگلیسی مقاله ISI
A study on optimising heat pipe geometrical parameters for sustainable passive cooling within the built environment
ترجمه فارسی عنوان
مطالعه ای در مورد بهینه سازی پارامترهای هندسی گرم گرما برای خنک کننده منفعل پایدار در محیط زیست
دانلود مقاله + سفارش ترجمه
دانلود مقاله ISI انگلیسی
رایگان برای ایرانیان
کلمات کلیدی
لوله حرارتی، خنک کننده منفعل، اسپانمن، پایداری، تونل باد،
موضوعات مرتبط
مهندسی و علوم پایه
مهندسی شیمی
جریان سیال و فرایندهای انتقال
چکیده انگلیسی
The way in which heat pipes are arranged plays an important role on the overall effectiveness of this sustainable thermal system. A numerical and experimental analysis into determining the optimum heat pipe streamwise distance for providing passive airside cooling in ventilation airstreams was carried out. The airflow and temperature profiles were numerically predicted using Computational Fluid Dynamics (CFD), the findings of which were quantitatively validated using wind tunnel experimentation. Using the heat pipe diameter (D) of 20âmm, the spanwise thicknesses were varied from 44âmm (St/D ratio of 2.2) to 52âmm (St/D ratio of 2.6). In order to ensure sustainable operation of the system, water was used as the heat pipe working fluid. Keeping the boundary conditions constant for all modes (inlet velocity of 2.3âm/s and inlet temperature of 314K), the rate of heat transfer was found to be directly proportional to the temperature difference between inlet and outlet interface. The findings determined that the spanwise thickness of 50âmm (St/D ratio of 2.5) provided the highest heat transfer in comparison to the other analysed models at 768âW. The overall effectiveness of the system was found to decrease from 5.6% to 4.7% when the spanwise thickness reduced from 50âmm to 44âmm. A good agreement was obtained between the numerical and experimental findings with a maximum error of 1.6% for temperature and 14.6% for velocity parameters. The investigation successfully evaluated the performance of heat pipes under varying geometrical arrangement, when utilised for the purpose of pre-cooling ventilation airstreams for a sustainable built environment.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 93, 25 January 2016, Pages 486-499
Journal: Applied Thermal Engineering - Volume 93, 25 January 2016, Pages 486-499
نویسندگان
Hassam Nasarullah Chaudhry,