Performance analysis of a waste heat driven activated carbon based composite adsorbent - Water adsorption chiller using simulation model
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Performance analysis of a waste heat driven activated carbon based composite adsorbent - Water adsorption chiller using simulation model
چکیده انگلیسی
This study aims at improving the performance of a waste heat driven adsorption chiller by applying a novel composite adsorbent which is synthesized from activated carbon impregnated by soaking in sodium silicate solution and then in calcium chloride solution. Modeling is performed to analyze the influence of the hot water inlet temperature, cooling water inlet temperature, chilled water inlet temperatures, and adsorption/desorption cycle time on the specific cooling power (SCP) and coefficient of performance (COP) of the chiller system with the composite adsorbent. The simulation calculation indicates a COP value of 0.65 with a driving source temperature of 85 °C in combination with coolant inlet and chilled water inlet temperature of 30 °C and 14 °C, respectively. The most optimum adsorption-desorption cycle time is approximately 360 s based on the performance from COP and SCP. The delivered chilled water temperature is about 9 °C under these operating conditions, achieving a SCP of 380 W/kg.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Heat and Mass Transfer - Volume 55, Issues 25–26, December 2012, Pages 7596-7610