Efficiency of free cooling using latent heat storage integrated into the ventilation system of a low energy building
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Efficiency of free cooling using latent heat storage integrated into the ventilation system of a low energy building
چکیده انگلیسی

This article presents the results of an investigation into the free cooling efficiency in a heavyweight and lightweight low energy building using a mechanical ventilation system with two latent heat thermal energy storages (LHTESs), one for cooling the fresh supply air and the other for cooling the re-circulated indoor air. Both LHTESs contain sphere encapsulated PCM (paraffin RT20). Using a developed and experimentally verified numerical model of the LHTES, the temperature response functions, based on the heat storage size, the air flow rates and the PCM's thermal properties, are established in the form of a Fourier series and empirical equations and used in the TRNSYS building thermal response model. Several mechanical ventilation, night cooling and free cooling operation modes were analysed and compared. It was found that the free cooling technique enables a reduction in the size of the mechanical ventilation system, provides more favourable temperatures and therefore enables better thermal comfort conditions, and in our studied case also fresh air for the occupants.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 30, Issue 1, January 2007, Pages 134–143
نویسندگان
, , ,