کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
1742650 1017705 2009 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
An improved thermal response test for U-tube ground heat exchanger based on optical fiber thermometers
موضوعات مرتبط
مهندسی و علوم پایه علوم زمین و سیارات ژئوشیمی و پترولوژی
پیش نمایش صفحه اول مقاله
An improved thermal response test for U-tube ground heat exchanger based on optical fiber thermometers
چکیده انگلیسی

As part of a new thermal response test (TRT) and to determine ground thermal conductivities, vertical temperature profiles were obtained using retrievable optical fiber sensors inserted into the U-tubes of two ground heat exchangers (GHEs) installed at Maebaru City (Fukuoka, Kyushu) and Kushiro City (Hokkaido), Japan. Measured profiles and outlet temperatures from TRTs were history-matched with the cylindrical source function. Nonlinear regression was used to estimate the vertical distribution of ground thermal conductivities. The computed distribution is consistent with measured data indicating both the reliability of the optical fiber thermometer and TRT interpretation. It is expected that TRTs and optical fiber thermometers will prove to be increasingly useful for optimizing the depth of the GHEs installed in heterogeneous formations, and consequently will minimize installation costs of geothermal heat pump systems.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Geothermics - Volume 38, Issue 4, December 2009, Pages 399–406
نویسندگان
, , , , , ,