Optimized mass flow rate distribution analysis for cooling the ITER Blanket System
چکیده انگلیسی


• Optimized water distribution in ITER blanket modules is presented.
• All key challenging constraints are included.
• The methodology and the successful result are presented.

This paper presents the rationale to the optimization of water distribution in ITER blanket modules, meeting both Blanket System requirements and interface compliance requirements.The key challenging constraints include to: be compatible with the overall water allocation (3140 kg/s for 440 wall mounted BMs); meet the critical heat flux margin of 1.4 in the plasma facing units; meet a maximum temperature increase of 70 °C at the outlet of each single BM; and ensure that water velocity is less than 7 m/s in all manifolds, and that the pressure drops of all BMs can be equilibrated. The methodology and the successful result are presented.