کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
4987231 | 1455146 | 2017 | 13 صفحه PDF | دانلود رایگان |

- Multi-objective optimization of induced draft cooling tower is reported.
- Maximization of performance and efficient energy utilization are addressed.
- User priority-based decision making approach is used with NSGA-II.
- New correlations for performance parameters are proposed.
- Proposed methodology can be implemented in diverse energy-based systems.
In the present work, a model based on experiments is presented to simultaneously optimize all possible performance parameters as well as to ensure minimum energy consumption from an induced draft cooling tower operating under a given set of conditions. Empirical correlations are obtained for performance parameters such as range, approach, tower characteristic ratio, effectiveness and evaporation rate against air and water flow rates, which in turn are selected as discrete objective functions to formulate a multi-objective optimization problem. Unlike previous studies which neglected the simultaneous consideration of five performance parameters aimed at minimum possible power consumption, here an unconstrained optimization of all objective functions is carried out using elitist Non-dominated Sorting Genetic Algorithm (NSGA-II). Considering five performance parameters, the air flow rate has been estimated under a given water flow rate using a Decision Making Matrix-based criterion. Among various performance parameters, the maximization of the range for diverse water flow rates implicitly satisfies different loads imposed on the cooling tower, thereby avoiding the necessity of formulating an additional constraint. Furthermore, due to maximization of the approach and minimization of the evaporation rate, minimum operating cost is ensured from the induced draft cooling tower.
Journal: Chemical Engineering Research and Design - Volume 123, July 2017, Pages 1-13