کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
588848 878609 2007 10 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Vent Sizing Criteria for Partial Volume Deflagration
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی بهداشت و امنیت شیمی
پیش نمایش صفحه اول مقاله
Vent Sizing Criteria for Partial Volume Deflagration
چکیده انگلیسی

The accidental spill of volatile solvents or the release of flammable gases within equipment and buildings is likely to form fuel concentration gradients unless efficient mixing is provided. As a consequence, even small amounts of fuel can form flammable clouds, and partial volume deflagrations may occur. Nevertheless, few indications are given in international guidelines for vent sizing and only over-conservative well-mixed stoichiometric assumptions are used. In this paper, we propose a predictive methodology for the evaluation of the dynamics of partial volume deflagration, aiming at defining useful correlations for the design of vent devices, starting from the fundamental equation for the rate of pressure rise and flame propagation in closed vessel. We define a ‘stratified gas deflagration index’ KG(m), where m is the filling ratio, and use it with the most common design equations for vent sizing. The approach has been validated by means of a CFD code for the simulation of stratified laminar methane–air explosion by varying both filling ratio and volume.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Process Safety and Environmental Protection - Volume 85, Issue 6, 2007, Pages 549–558
نویسندگان
, , , ,