کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
648244 | 1457196 | 2010 | 5 صفحه PDF | دانلود رایگان |

The purpose of the present study is to enhance the heating capacity and increase COP under the frosting condition during heating operation of small capacity air-to-air heat pump. We applied an electric heater in front of outdoor unit of heat pump instead of indoor unit as usual. When the outdoor temperature is 2 °C/1 °C (DB/WB), the present heat pump turns on the electric heater in outdoor unit. The heating capacity increases 38.0% and COP increases 57.0% in comparison with those of conventional heat pump. When the outdoor temperature is 4 °C/2 °C (DB/WB), the electric heater is in ON/OFF mode according to the temperature of the evaporator. The heating capacity increases 9.1% and COP increases 71.1% in comparison with those of conventional heat pump.
Journal: Applied Thermal Engineering - Volume 30, Issues 6–7, May 2010, Pages 539–543