کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
648533 1457200 2009 6 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Single-phaseexperimental analysis of heat transfer in helically finned heat exchanger
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Single-phaseexperimental analysis of heat transfer in helically finned heat exchanger
چکیده انگلیسی

A methodology for designing helically serrated finned tube heat exchanger based on the logarithmic Mean Temperature Difference (LMTD) method is validated with experimental tests. The method uses semi-empirical correlations for calculating convective coefficients both inside and outside staggered tube bundles. Equipment was designed, built, and installed in a paper factory in order to validate the methodology. Comparisons between predictions and experimental data show a precision of approximately 96% in heat transfer and approximately 90% in pressure drop for Reynolds numbers upper to 10,000.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 29, Issues 11–12, August 2009, Pages 2205–2210
نویسندگان
, , , ,