کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
648716 1457201 2009 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Numerical study on the dispersion of airborne contaminants from an isolation room in the case of door opening
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Numerical study on the dispersion of airborne contaminants from an isolation room in the case of door opening
چکیده انگلیسی
A negative pressure isolation room is built to accommodate and cure patients with highly infectious diseases. An absolutely airtight space effectively prevents infectious diseases from leaking out of the isolation room. Opening the door leads to a breakdown in isolation conditions and causes the dispersion of infectious air out of the isolation room. Extensively employed to manage smoke in cases of fires at subway and highway tunnels, a concept of controlling airflow is applied to the study. This study proposes a design of ventilation system to control air flow rate for containing airborne contaminant and preventing its spread to the adjacent rooms when the door to the isolation room is opened and closed. This paper employs computational fluid dynamics (CFD) as a more effective approach to examine the concentration maps of airborne contaminants and the airflow patterns of room air and discuss the influence of temperature differences between two rooms on airborne dispersion. Results show that an air velocity above 0.2 m/s via a doorway effectively prevents the spread of airborne contaminants out of the isolation room in the state of door opening.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 29, Issues 8–9, June 2009, Pages 1544-1551
نویسندگان
, , ,