This study investigates the effect of fin pitches and fin materials on the air-side performance of crimped fin-and-tube heat exchangers in the range of high Reynolds numbers (4000–13000). The test samples are made from copper and aluminium with different fin pitches (fp = 3.2, 4.2 and 6.2 mm). It is found that the proposed simple average effectiveness equation from the pure counter and parallel circuitry arrangement can well represent the effectiveness-NTU relationship for the current z-shape arrangement. The experimental results reveal that the fin pitch casts insignificant effect on the heat transfer characteristics (Colburn j factor). However, a detectable rise of the friction factor is seen when the fin pitch is increased to fp = 6.2 mm. On the other hand, the effect of fin material on the airside performance is negligible.
Journal: International Journal of Heat and Mass Transfer - Volume 54, Issues 9–10, April 2011, Pages 2234–2240