کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
7045888 1457096 2018 7 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Performance estimation of ejector cycles using ethers and fluorinated ethers as refrigerants
ترجمه فارسی عنوان
برآورد عملکرد چرخه های انژکتور با استفاده از اترها و اکسید فلوراید به عنوان مبرد
کلمات کلیدی
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
چکیده انگلیسی
Computer software, based on the theoretical model of Huang et al. (1999) with thermodynamic properties of selected refrigerants, was prepared. The investigation was focused on alternative refrigerants that belong to the groups of ethers and fluorinated ethers. The main purpose of the paper was to check the possibility of co-operating the above substances with an ejector cooling system powered by a high-temperature heat source. A series of calculations were carried out for the generator temperature from 60 °C to 165 °C, with assumed temperatures of evaporation of 10 °C and condensation of 40 °C. The analysis revealed that there is no single refrigerant that ensures the efficient operation of the system in the whole range of primary vapor temperatures. Each substance has its own maximum entrainment ratio and COP at its individual optimum temperature. The maximum COP values were obtained for dimethyl ether and diethyl ether, and reached 0.30 and 0.25 respectively.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 133, 25 March 2018, Pages 269-275
نویسندگان
, ,