Thermal performance and pressure drop of spiral-tube ground heat exchangers for ground-source heat pump
ترجمه فارسی عنوان
عملکرد حرارتی و افت فشار مبدلهای حرارتی زمین مارپیچ برای پمپ حرارتی منبع زمین
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
چکیده انگلیسی
Thermal performance and pressure drop of the spiral-tube GHE were evaluated in this present work. A numerical simulation tool was used to carry out this research. The heat exchange rates per meter borehole depth of the spiral-tube GHE with various pitches and their pressure drops were compared with that of the U-tube GHE. Furthermore, a comparative analysis between a spiral pipe and straight pipe was performed. In comparison with the straight pipe, using the spiral pipe in the borehole increased the heat exchange rate to the ground per meter borehole depth. However, the pressure drop of water flow also increased due to increasing the length of pipe per meter borehole depth and its spiral geometry. The accuracy of the numerical model was verified for its pressure drop with some pressure drop correlations. The heat exchange rate and pressure drop of the GHEs are presented. As an example, the heat exchange rate per meter borehole depth of spiral pipe with 0.05 m pitch in the turbulent flow increased of 1.5 times. Its pressure drop also increased of 6 times. However, from the view point of energy efficiency, using the spiral pipe in the ground-source heat pump system gives a better performance than using the straight pipe. The heat exchange rate and pressure drop are important parameter in design of the ground-source heat pump (GSHP) system.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 90, 5 November 2015, Pages 630-637
نویسندگان
, ,