Velocity and temperature attenuation of a ceiling-jet along a horizontal tunnel with a flat ceiling and natural ventilation
ترجمه فارسی عنوان
کاهش سرعت و درجه حرارت یک سقف جت در امتداد تونل افقی با سقف تخت و تهویه طبیعی
کلمات کلیدی
آتش تونل، سقف جت، ضعیف شدن سرعت، کاهش دما، تعداد استنتون، شماره ریچاردسون
موضوعات مرتبط
مهندسی و علوم پایه علوم زمین و سیارات مهندسی ژئوتکنیک و زمین شناسی مهندسی
چکیده انگلیسی


• Correlation to estimate the attenuation in ceiling-jet velocity was developed.
• Correlation for the attenuation in ceiling-jet temperature rise was also developed.
• Variation in Richardson number of ceiling-jet with distance was estimated.

A series of fire tests was conducted in a small-scale tunnel with dimensions of 10.0 m (L) × 0.75 m (W) × 0.45 m (H) and a rectangular cross-section. Detailed measurements of the velocity and temperature within a steady fire-driven ceiling-jet running along the centre of the ceiling were conducted.Referring to a theoretical derivation process described in the literature as a starting point, correlations representing the velocity and temperature attenuation along the tunnel axis were developed.The values of the coefficients included in the developed correlation for the velocity attenuation were measured using a particle image velocimetry system during the experiments conducted in the small-scale tunnel. The value of the Stanton number was determined by considering the ceiling-jet thickness, which was derived from the velocity distribution. The values of the coefficients included in the developed correlation for the temperature attenuation were also determined based on experimental results described in the literature, which were obtained in a large-scale tunnel constructed using good heat insulation properties.Through these correlations developed for the velocity and temperature attenuations along the tunnel axis, the variation in the Richardson number of the ceiling-jet based on the distance from the fire source position along the tunnel axis was examined, and the position where the ceiling-jet changed from a shooting flow to a tranquil flow was determined. The boundary positions between the shooting and tranquil flows were determined using correlations between the velocity and/or temperature attenuation, which were compared with the variation in the Richardson number along the tunnel axis to verify their appropriateness.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Tunnelling and Underground Space Technology - Volume 56, June 2016, Pages 79–89