کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
4481183 1623097 2015 13 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Temperature diagnostic to identify high risk areas and optimize Legionella pneumophila surveillance in hot water distribution systems
ترجمه فارسی عنوان
تشخیص دما برای شناسایی مناطق پر خطر و بهینه سازی نظارت بر لژیونلا پنوموفیلا در سیستم های توزیع آب گرم
موضوعات مرتبط
مهندسی و علوم پایه علوم زمین و سیارات فرآیندهای سطح زمین
چکیده انگلیسی


• Temperature profiles were generated for hot water distribution systems points-of-use.
• Risk assessment based on temperature profile results at control points was developed.
• L. pneumophila positive areas were predicted using the risk assessment tool.
• A temperature diagnostic flowchart is proposed to identify L. pneumophila risk areas.

Legionella pneumophila is frequently detected in hot water distribution systems and thermal control is a common measure implemented by health care facilities. A risk assessment based on water temperature profiling and temperature distribution within the network is proposed, to guide effective monitoring strategies and allow the identification of high risk areas. Temperature and heat loss at control points (water heater, recirculation, representative points-of-use) were monitored in various sections of five health care facilities hot water distribution systems and results used to develop a temperature-based risk assessment tool. Detailed investigations show that defective return valves in faucets can cause widespread temperature losses because of hot and cold water mixing. Systems in which water temperature coming out of the water heaters was kept consistently above 60 °C and maintained above 55 °C across the network were negative for Legionella by culture or qPCR. For systems not meeting these temperature criteria, risk areas for L. pneumophila were identified using temperature profiling and system's characterization; higher risk was confirmed by more frequent microbiological detection by culture and qPCR. Results confirmed that maintaining sufficiently high temperatures within hot water distribution systems suppressed L. pneumophila culturability. However, the risk remains as shown by the persistence of L. pneumophila by qPCR.

Figure optionsDownload high-quality image (195 K)Download as PowerPoint slide

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Water Research - Volume 71, 15 March 2015, Pages 244–256
نویسندگان
, , , , , , , , ,