کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
7167717 1462942 2018 13 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Failure of a sag water pipe triggered by aging of the GFRP composite relining
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی صنعتی و تولید
پیش نمایش صفحه اول مقاله
Failure of a sag water pipe triggered by aging of the GFRP composite relining
چکیده انگلیسی
The investigation led to the conclusion that aging had progressed significantly in the centrifuged GFRP pipes. However, this alone would not have precipitated the failure. The partially incomplete backfilling between the composite relining and the original steel pipe had locally increased the stresses in the composite shell considerably due to hoop bending stresses. Hence, only the combination of both effects with a reduction of the composite shell strength due to aging and additional local loads could explain the delayed failure of the pipe after 12 years of operation.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Engineering Failure Analysis - Volume 84, February 2018, Pages 358-370