کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
4483773 1316899 2012 11 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Impact of advanced water conservation features and new copper pipe on rapid chloramine decay and microbial regrowth
موضوعات مرتبط
مهندسی و علوم پایه علوم زمین و سیارات فرآیندهای سطح زمین
پیش نمایش صفحه اول مقاله
Impact of advanced water conservation features and new copper pipe on rapid chloramine decay and microbial regrowth
چکیده انگلیسی

Taste and odor issues occurring in new buildings were attributed to rapid loss of chloramine residual, high levels of microbes in the potable water system, and high water age due to use of advanced water conservation devices. Laboratory experiments confirmed that chloramine could decay rapidly in the presence of new copper pipe, providing a possible explanation for the rapid disinfectant loss in the new buildings. Higher temperature and lower pH also accelerated the rate of chloramine decay in copper pipes. The reaction was slowed by the addition of phosphate inhibitor or aluminum, which presumably formed barriers between the pipe wall and the chloramine in the bulk water. Additional research is needed to better understand how to maintain high quality water in buildings while also conserving water.


► Rapid chloramine residual loss can occur in copper pipe.
► Disinfectant decay can lead to microbial regrowth.
► These problems can occur in new buildings with water conservation features.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Water Research - Volume 46, Issue 3, 1 March 2012, Pages 611–621
نویسندگان
, , ,